SU3000XL - Overview

3000VA / 3kVA / 2400 watt on-line, double-conversion UPS system for critical server, network and telecommunications equipment. Attractive upright tower format. Expandable battery runtime with optional BP72V15-2U (limit 1), BP72V28RT-3U (multi-pack compatible) and BP72V18-2US (multi-pack compatible) external battery packs. Full time sine wave 110/120V output with +/-2% voltage regulation. Uninterruptible Power Supply (UPS) actively converts raw incoming AC power to DC, then re-converts output back to completely regulated, filtered AC output. Operates continuously without using battery power during brownouts to 65V and overvoltages to 150V. Up to 97% efficiency in optional economy mode saves BTU heat output and energy costs. NEMA L5-30P input plug. NEMA L5-30R, NEMA 5-15/20R and NEMA 5-15R output receptacles. Network-grade AC surge and noise suppression. Zero transfer time between AC and battery operation. Network management interfaces include USB port, DB9 serial port and SNMPWEBCARD slot. Built-in DB9 port offers both enhanced RS-232 enabled monitoring data, plus contact closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and mains power conditions via all network interfaces. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. Integrated two bank PDU switching supports automated load shedding and remote-reboot of connected equipment. Multi-stage metered current monitoring and battery charge status LEDs. Mains power and voltage regulation LEDs. Audible Alarm. Self-test. Fault-tolerant auto-bypass mode. Field replaceable, hot swappable internal batteries and external battery packs. $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only).

What does Uninterruptible Power Supply (UPS) mean?
An uninterruptible power supply (UPS) provides nearly instantaneous power when the main utility power source fails, allowing either time for power to return or for the user to shut down the system or equipment normally by closing running computer system applications and using the operating system to shut down the system. The user has between five and 15 minutes to shut down a system normally or bring an auxiliary power source online to restore the power supply. In addition, most UPS systems also work to address power source electrical surges, sag voltage, voltage spikes, frequency instability, noise interference or harmonic distortion from the ideal sinusoidal wave form. If you're concerned about power failures, especially if you've lost work on your computer due to power outages in the past, you should buy a UPS. A UPS combines a surge suppressor with a big battery, and has special circuitry that detects a power failure and quickly switches over to run your equipment on its battery. The sole purpose of a UPS is to give you a few minutes at the start of a power failure to do two things:
-Save your work, and
-Shut down your computer.
Please Note: A UPS is not designed to let you continue to use your computer for hours and hours until the power comes back on. If properly chosen, a UPS will give you 5 to 10 minutes (possibly more) to save and do an orderly shutdown.

  • Specifications:

    • Output Volt Amp Capacity (VA) 30000
    • Output kVA Capacity (kVA) 30
    • Output Watt Capacity (Watts) 24000
    • Output kW Capacity (kW) 24
    • Power Factor 0.8
    • Crest Factor 0.125694444444444
    • Nominal Output Voltage(s) Supported 120/208V; 3-Phase Wye
    • Frequency Compatibility 50 / 60 Hz
    • Output Voltage Regulation (Line) +/- 2%
    • Output Voltage Regulation (Battery) +/- 2%
    • Output Receptacles Hardwire
    • Output AC Waveform (AC ) Pure Sine wave
    • Output AC Waveform (Battery) Pure Sine wave
    • Rated input current (MaxLoad) 90A (per phase, online)
    • Nominal Input Voltage(s) Supported 120/208V AC (3ph wye)
    • Nominal Input Voltage Description 3-Phase Wye, 4 wire (L1, L2, L3, N, G)
    • UPS Input Connection Type Hardwire
    • Input Phase 3-Phase
    • Full Load Runtime 11 min. (24kw)
    • Half Load Runtime 25 min. (12kw)
    • Expandable Battery Runtime Supports extended runtime with optional external battery packs
    • External Battery Pack Compatibility SURBC2030; SUBF2030 (holds 4 SURBC2030)
    • Expandable Runtime Description Includes a battery housing with space for 3 internal SURBC2030 battery packs for extended runtime. Additional runtime capacity is available by adding SUBF2030 and additional SURBC2030 batteries - see runtime chart for specific recommendations
    • DC System Voltage (VDC) 240
    • Battery Recharge Rate (Included Batteries) 2 - 4 hours from 10% to 90%
    • Internal UPS Replacement Battery Cartridge SURBC2030
    • Battery Access Front panel internal battery access door
    • Battery Replacement Description Hot-swappable, replaceable batteries
    • Voltage Regulation Description Online, double-conversion power conditioning
    • Overvoltage Correction Maintains continuous operation without using battery power during overvoltages to 144 / 250 (3-Phase, 4-Wire, wye), reducing output within 2% of nominal
    • Undervoltage Correction Maintains continuous operation without using battery power during brownout / undervoltage conditions to 96 / 166 (3-Phase, 4-Wire, wye)
    • Front Panel LCD Display SELECTABLE LCD DISPLAY: indicates a wide range of UPS operational and fault/warning conditions including operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage and more (see manual)
    • Switches ON button turns UPS's inverter ON. "OFF" button turns UPS's inverter OFF. "Select" Button browses through items displayed on LCD screen. "Enter" button selects items displayed on LCD screen. "Select" and "Enter" buttons used simultaneously mute UPS alarms. "Battery Start" Switch cold starts the inverter. "Emergency Power Off" button turns UPS output OFF and disables Bypass output. "Manual Bypass" switch bypasses the UPS's inverter during maintenance.
    • Alarm Cancel Operation Power-fail alarm can be silenced using alarm-cancel switch
    • Audible Alarm Alarms warn against a variety of operational conditions: low-battery, overload, shutdown, bypass and more
    • LED Indicators 7 LED DISPLAY: AC input, bypass input, AC-DC charger, DC-AC inverter, AC output, bypass operation and battery operation
    • EMI / RFI AC Noise Suppression Yes
    • AC Suppression Joule Rating 2032
    • AC Suppression Response Time Instantaneous
    • Installation Form Factors Supported with Included Accessories Tower
    • Primary Form Factor Tower
    • UPS Power Module Dims 50.9" x 19.5" x 36.8"
    • UPS Power Module Weight 69.3 lbs
    • UPS Shipping Dimensions 61.5" x 31" x 44.5"
    • Shipping Weight 75.2 lbs
     