SU5000RT3UHV - Overview

Tripp Lite 5kVA Smart Online RM UPS. 5000VA on-line, double-conversion UPS for server, network and telecommunications equipment. Maintains battery derived AC output during blackouts with active, full-time power conditioning. Fault-tolerant auto-bypass prevents unexpected service interruptions during overload or internal fault conditions. Full-time sine wave output within 2% of selectable 200/208/220/230/240V AC. Corrects brownouts to 156V and overvoltages to 276V. Frequency regulation locks output power to 50/60Hz (+/-0.2%)/Expandable runtime with optional rackmount external battery packs. Double-conversion UPS converts raw input from AC to DC, then back to perfect sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Network-grade AC surge and noise suppression. Network management interfaces include 2 DB9 ports and SNMPWEBCARD slot. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all 3 network interfaces. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. Front panel LEDs and LCD readout with scroll controls support visual monitoring of all major UPS functions. Power Distribution Unit (PDU) options supported. $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only).


What does Uninterruptible Power Supply (UPS) mean?
An uninterruptible power supply (UPS) provides nearly instantaneous power when the main utility power source fails, allowing either time for power to return or for the user to shut down the system or equipment normally by closing running computer system applications and using the operating system to shut down the system. The user has between five and 15 minutes to shut down a system normally or bring an auxiliary power source online to restore the power supply. In addition, most UPS systems also work to address power source electrical surges, sag voltage, voltage spikes, frequency instability, noise interference or harmonic distortion from the ideal sinusoidal wave form. If you're concerned about power failures, especially if you've lost work on your computer due to power outages in the past, you should buy a UPS. A UPS combines a surge suppressor with a big battery, and has special circuitry that detects a power failure and quickly switches over to run your equipment on its battery. The sole purpose of a UPS is to give you a few minutes at the start of a power failure to do two things:
-Save your work, and
-Shut down your computer.
Please Note: A UPS is not designed to let you continue to use your computer for hours and hours until the power comes back on. If properly chosen, a UPS will give you 5 to 10 minutes (possibly more) to save and do an orderly shutdown.

  • Specifications:

    • Output Capacity Details Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as the overload is cleared
    • Output Volt Amp Capacity (VA) 5000
    • Output kVA Capacity (kVA) 5
    • Output Watt Capacity (Watts) 4500
    • Output kW Capacity (kW) 4.5
    • Power Factor 0.9
    • Crest Factor 0.125694444444444
    • Nominal Output Voltage(s) Supported 200V; 208V; 240V
    • Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
    • Frequency Compatibility Details Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating)
    • Output Voltage Regulation (Line Mode) +/- 2%
    • Output Voltage Regulation (Economy Line Mode) +/- 10%
    • Output Voltage Regulation (Battery Mode) +/- 2%
    • Output Receptacles (2) L6-20R; (2) L6-30R
    • Output Circuit Breakers 20A breaker protects L6-20R outlets, L6-30R outlets are unbreakered
    • Output AC Waveform (AC Mode) Pure Sine wave
    • Output AC Waveform (Battery Mode) Pure Sine wave
    • Rated input current (Max Load) 24A (200V), 24A (208V), 23.6A (220V), 23A (230V), 21.7A (240V)
    • Nominal Input Voltage(s) Supported 200V AC; 208V AC; 240V AC
    • Nominal Input Voltage Description Factory configured to 208V
    • UPS Input Connection Type L6-30P
    • UPS Input Cord Length 10'
    • Recommended Electrical Service 30A
    • Input Phase Single-Phase
    • Full Load Runtime 3.5 minutes (4500 watts)
    • Half Load Runtime 11 minutes (2250 watts)
    • Expandable Battery Runtime Supports extended runtime with optional external battery packs
    • External Battery Pack Compatibility BP192V1037C-1PH; BP192V12-3U; BP192V1407C-1PH; BP192V557C-1PH; BP192V787C-1PH; BP192V5RT2U (limit 1)
    • DC System Voltage (VDC) 192
    • Battery Recharge Rate (Included Batteries) 6 hours from 10% to 90% (typical, full load discharge)
    • Internal UPS Replacement Battery Cartridge RBC5-192 (qty 1)
    • Battery Access Front panel battery access
    • Battery Replacement Description Hot-swappable, user replaceable batteries
    • Voltage Regulation Description Online, double-conversion power conditioning
    • Overvoltage Correction 2% output voltage regulation during overvoltages to 280V (full load) / 300V (90% load or less)
    • Undervoltage Correction 2% output voltage regulation during undervoltages to 156V (full load) / 100V (50% load or less)
    • Front Panel LCD Display Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats (see manual)
    • Switches 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; A manual bypass switch featured on the detachable PDU allows for complete removal of the UPS during routine maintenance without disrupting power to connected loads
    • Alarm Cancel Operation Alarm cancel switch
    • Audible Alarm Unique audible alarms for all major UPS, environmental and power conditions (see manual)
    • LED Indicators 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options
    • UPS AC Suppression Response Time Instantaneous
    • EMI / RFI AC Noise Suppression Yes
    • Included Mounting Accessory Description 4 post rackmount installation accessories included
    • Installation Form Factors Supported with Optional Accessories 2 post rackmount (2POSTRMKITHD); Tower (2-9USTAND)
    • Primary Form Factor Rackmount
    • UPS Power Module Dims 6.85" x 17.5" x 20.7"
    • Rack Height 4U
    • UPS Power Module Weight 113.6 lbs
    • UPS Shipping Dimensions 12.7" x 23.6" x 29.1"
    • Shipping Weight 151.8 lbs
     
  • GTIN: