The SurgeX SX1115 provides guaranteed surge protection and power conditioning for audio, video, broadcast and computer equipment.

The units are 15-amp load-capable and have 8 industrial grade grounded AC receptacles (6 switched; 2 always on) plus a front-panel courtesy receptacle.

The unit features both common mode and normal mode Impedance Tolerant EMI/RFI filtering for a comprehensive power conditioning solution.

SurgeX Advanced Series Mode technology is superior to conventional MOV circuitry or MOV-Hybrid designs and is completely non-sacrificial. Our zero let-through technology provides the most reliable protection available. It stops all surges up to 6,000 volts (unlimited surge current) without producing harmful side effects such as ground contamination or common-mode disturbances.

  • Features:

    • Magnetic shielding steel enclosure
    • 9' grounded 3-wire #14 line cord
    • 8 grounded AC outlets on rear panel (6 switched, 2 always on)
    • Front panel courtesy receptacle
    • Advanced Series Mode surge protection
    • Advanced Impedance Tolerant EMI/RFI filtering
    • Thermal circuit breaker overload protection
    • Self-test circuit with visual indicator
    • 10-year warranty
    • Made in U.S.A.
     
  • Specifications:

    • Load Rating: 15 amps @ 120 volts
    • Power Requirement (no load): 10 watts
    • Surge Let-Through Voltage (6000-volt surge): 0 volts
    • UL 1449 Adjunct Classification Test Results:
    • 1000 surges, 6000 volts, 3000 amps, B3 pulse.
    • Measured suppressed voltage: 170 volts, no failures
    • Federal Guidelines:
    • Grade A, Class 1, Mode 1 (CID A-A-55818)
    • EMI/RFI Filter, Normal Mode (50-ohm load):
    • 40 dB @ 100 kHz; 50 dB @ 300 kHz;
    • 50 dB @ 3 MHz; 50 dB @ 30 MHz
    • EMI/RFI Filter, Common Mode (50-ohm load):
    • 18 dB @ 300 kHz; 30 dB @ 1 MHz;
    • 50 dB @ 5 MHz; 50 dB @ 20 MHz
    • Maximum Applied Surge Voltage: 6000 volts*
    • Maximum Applied Surge Current:
    • Unlimited, due to current limiting*
    • Maximum Applied Surge Energy:
    • Unlimited, due to current limiting*
    • Endurance (C62.41-1991 Category B3 pulses):
    • 1 kV>500,000; 3 kV>10,000; 6 kV>1000
    • Dimensions: 1.75" H x 19" W x 10.5" D (4.5 x 48.3 x 26.7 cm)
    • Weight: 11 lbs (5 kg)
    • Temperature Range: 5§ to 35§ C
    • Humidity Range: 5% to 95% R.H., non-condensing
    • Agency Listings: ETL and cETL (UL 1449, 2nd edition;
    • CSA C22.2 No.8-M1986, R2000)
     