Tripp Lite SU12000RT4UHW 12000VA 8400W UPS Smart Online Rackmount 12kVA PDU 120V-240V 8U

ITEM #: TRL-SU12RT4UHW MFG #: SU12000RT4UHW

Primary Image
  • Product Image Thumbnail 1 of 4
  • Product Image Thumbnail 2 of 4
  • Product Image Thumbnail 3 of 4
  • Product Image Thumbnail 4 of 4

This item is no longer available.
Ask a Markertek Expert if you need assistance finding an appropriate substitute.

(800) 522-2025Email

Items similar to the TRL-SU12RT4UHW

SU12000RT4UHW - Overview

Tripp Lite's SU12000RT4UHW SmartOnline Hot-Swappable Modular Rack/Tower UPS System provides 12,000VA (12kVA) on-line, double-conversion UPS support for server, network and telecommunications equipment. Maintains battery-derived AC output during blackouts with active, full-time power conditioning. Fault-tolerant auto-bypass prevents unexpected service interruptions during overload or internal fault conditions. 4U power module and 4U external battery pack installs in 8 rack spaces (8U). Upright tower and two-post rackmount installation supported with optional accessories. Maintains full-time sine wave output within 3% of selectable 208/120 or 240/120V AC. Corrects brownouts and overvoltages from 65V to 140V (L-N). Expandable runtime with optional external battery packs. Converts raw input from AC to DC, then resynthesizes output power back to perfect sine wave AC output with enhanced protection from harmonic distortion, fast electrical impulses and other hard-to-solve power problems not addressed by other UPS types. Highly efficient operation in optional economy mode setting, saving BTU heat output and energy costs. Network-grade AC surge and noise suppression. Network management interfaces include combination DB9 RS-232 enabled and dry contact serial port, enhanced USB port and SNMPWEBCARD slot. HID-compliant USB interface enables integration with built-in power management and auto-shutdown features of Windows and Mac OS X. Supports simultaneous detailed monitoring of equipment load levels, self-test data and utility power conditions via all three network interfaces. Includes PowerAlert monitoring software and complete cabling. Supports Emergency Power Off (EPO) via built-in interface. Front panel LEDs and LCD readout with scroll controls support visual monitoring of all major UPS functions. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations. Split-phase, four-conductor hardwire input. UPS supports hardwire output. Output hardwire connections are mounted on a detachable backplate with manual bypass switch to enable hot-swappable UPS replacement without powering off connected equipment. External battery packs are field replaceable and hot swappable. Attractive all-black color scheme. $250,000 Ultimate Lifetime Insurance (U.S., Canada, and Puerto Rico only).

What does Uninterruptible Power Supply (UPS) mean?
An uninterruptible power supply (UPS) provides nearly instantaneous power when the main utility power source fails, allowing either time for power to return or for the user to shut down the system or equipment normally by closing running computer system applications and using the operating system to shut down the system. The user has between five and 15 minutes to shut down a system normally or bring an auxiliary power source online to restore the power supply. In addition, most UPS systems also work to address power source electrical surges, sag voltage, voltage spikes, frequency instability, noise interference or harmonic distortion from the ideal sinusoidal wave form. If you're concerned about power failures, especially if you've lost work on your computer due to power outages in the past, you should buy a UPS. A UPS combines a surge suppressor with a big battery, and has special circuitry that detects a power failure and quickly switches over to run your equipment on its battery. The sole purpose of a UPS is to give you a few minutes at the start of a power failure to do two things:
-Save your work, and
-Shut down your computer.
Please Note: A UPS is not designed to let you continue to use your computer for hours and hours until the power comes back on. If properly chosen, a UPS will give you 5 to 10 minutes (possibly more) to Save and do an orderly Shutdown

  • Features:

    • Product Warranty Period (Worldwide) 2-year limited warranty
    • Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250,000 Ultimate Lifetime Insurance
     
  • Specifications:

    • Output Capacity Details 12,000VA, 8400W (240V) / 10,395VA, 8400W (208V); Supports up to 105% load continuously in double conversion mode, 106 to 125% for 3 minutes, 126 to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support equipment directly from mains power; Double conversion mode is automatically restored as the overload is cleared
    • Output Volt Amp Capacity (VA) 12000
    • Output kVA Capacity (kVA) 12
    • Output Watt Capacity (Watts) 8400
    • Output kW Capacity (kW) 8.4
    • Power Factor 0.7
    • Crest Factor 0.125694444444444
    • Nominal Output Voltage(s) Supported 120V; 208V; 240V
    • Nominal Voltage Details 240/120V or 208/120V split phase output
    • UPS Input Connection Type Hardwire
    • UPS Input Connection Description 4 wire split-phase input (L1, L2, N, G)
    • Recommended Electrical Service 50A 208/240-120 Split Phase
    • Input Phase Single-Phase
    • Full Load Runtime (min.) 7 min. (8400w)
    • Half Load Runtime (min.) 20 min. (2400w)
    • Expandable Battery Runtime Supports extended runtime with optional external battery packs
    • External Battery Pack Compatibility BP192V18-4U; BP192V557C-16K; BP192V787C-16K; BP192V1037C-16K; BP192V1407C-16K
    • DC System Voltage (VDC) 192
    • Battery Recharge Rate (Included Batteries) Less than 6 hours from 10% to 80% (typical, full load discharge)
    • Battery Replacement Description Hot-swappable, user replaceable external battery packs
    • Voltage Regulation Description +/-3% output voltage regulation in online, double-conversion mode
    • Overvoltage Correction Corrects overvoltages to 140 (measured L1-N : L2-N)
    • Undervoltage Correction Corrects undervoltages to 65V (measured L1-N : L2-N)
    • UPS AC Suppression Response Time Instantaneous
    • EMI / RFI AC Noise Suppression Yes
    • Included Mounting Accessory Description 2 sets of adjustable 4 post rack rails included
    • UPS Power Module Dimensions (hwd, in.) 7 x 17.5 x 33.9
    • Installed Whole System Maximum Rack Depth (in.) 40.5
    • Rack Height 8U
    • UPS Power Module Weight (lbs.) 86
    • UPS Dimensions Details Includes 4U battery pack, 4U power module and detachable output PDU; Installed whole system rack depth specification indicates the depth of the UPS power module with the PDU attached
    • Included Battery Pack Dimensions 7" x 17.5" x 27.8"
    • Included Battery Pack Weight 239 lbs
    • UPS Shipping Dimensions 45.5" x 23.5" x 34.5"
    • Shipping Weight 448.8 lbs
    • Cooling Method Fan
    • UPS Housing Material Steel
    • Operating Temperature Range +32 to +104 degrees
    • Storage Temperature Range +5 to +122 degrees
    • Relative Humidity 0 to 95%, non-condensing
    • Low Voltage Transfer to Battery Power (Setpoint) 65V (L1-N:L2-N)
    • High Voltage Transfer to Battery Power (Setpoint) 140V (L1-N:L2-N)
    • Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
     
  • GTIN:

    0037332154873
     

SU12000RT4UHW - Required Accessories

    California Residents:
    WARNING:
    Cancer and Reproductive Harm - www.P65Warnings.ca.gov